SR114H "Standard Grade"
Control Cables - Screened 300/500V
Temperature rating : -40 °C ÷ +90 °C
(for insulated conductor only: max 200 °C)
Dielectric test    : 2000 V r.m.s. x 5’ (core/core)
Insulation resistance :

≧300 MΩ x km (at 20 °C)

Short circuit temperature : 350 °C
Construction  
Conductor : plain annealed copper wire
Insulation : fire resistant silicone rubber EI2 to BS7655: Section 1.1
Cabling : cores cabled together in concentric layers
Overall screen :

aluminium / polyester tape with non insulated tinned

    copper earth or drain waire
Sheath :

thermoplastic LSZH LTS3 to BS 7655: section 6.1

     

*FIRECEL SR 114H are manufactured and tested according to BS 7629 and are included in new fire alarm code of practice BS 5839-1: 2002 clause 26.2d).

Product Certificates No. 217e / No. 217f assessed to BS 5839-1 Standard BS 7629, BS 7622 BS 6425: Part 1 and BS 6387 CWZ (cables up to 4 cores 4.0 sqmm)

 

 

 

 

 

 

 

 

 

Standards
BS 4066
BS 5839-1 Standard
BS 6387 C W Z
BS 7629
BS 8434-1:2003
SS 299 part 1
IEC 60331
IEC 60332-1
IEC 60332-3A
IEC 60754-1
IEC 61034
EN 50200 PH30
EN 50266-2