Rubber & Crane Cables :638 TQ
EPR/HOFR 638 TQ Heavy Duty Trailing Flexible Rubber Cable, Single & Multicore EPR Insulated CSP Sheathed 450/750V to BS 6007
CONSTRUCTION :
Conductor: Flexible Class 5 Tinned Copper to BS6360
Insulation: Ethylene Propylene Rubber (EPR), Type GP1 to BS 7655
Sheath: Chlorosulphonated Polythylene (CSP) Type RS4 to BS 7655 H.O.F.R. Heat and Oil Resistant Flame Retardant
APPLICATION :
Designed primarily as a trailing cable for use in the power, mains supply or extension leads when there is a requirement for heavy duty tough rubber flexible cable.
TECHNICAL DATA :
Voltage: 450/750V
Operating Temperature Range: -20oC to +85Oc
Bending Radius: 6 x cable diameter for cables not exceeding 25mm2
8 x cable diameter for cables exceeding 25mm2
RELEVANT STANDARDS :
To BS6007 1975 Table 4.
CORE IDENTIFICATION :
1 Cores: Black
2 Cores: Blue, Br ow
5 Cores: Green/Yellow, Black, Blue, Brown, Black
6 Cores +: White cores with Black numbers.
6381TQ Single Core Type 450/750V EPR/HOFR Trailing Rubber Cable
Core and Size
Mm sq |
Stranding (Number of Strand/Strand Diameter |
Nominal Thickness of Insulation mm |
Nominal Overall Diameter mm |
1 X 4.0 |
56/0.30 |
1.0 |
7.8 |
1 X 6.0 |
84/0.30 |
1.0 |
9 |
1 X 10.0 |
80/0.40 |
1.2 |
10.8 |
1 X 16.0 |
126/0.40 |
1.2 |
12.1 |
1 X 25.0 |
196/0.40 |
1.4 |
14.1 |
1 X 35.0 |
276/0.4 |
1.4 |
15.9 |
1 X 50.0 |
396/0.40 |
1.6 |
18.5 |
1 X 70.0 |
360/0.50 |
1.6 |
21 |
1 X 95.0 |
475/0.50 |
1.8 |
23.9 |
1 X 120.0 |
608/0.50 |
1.8 |
25.8 |
1 X 150.0 |
756/0.50 |
2.0 |
28.6 |
1 X 185.0 |
925/0.50 |
2.2 |
31.5 |
1 X 240.0 |
1221/0.50 |
2.4 |
35.1 |
1 X 300.0 |
1525/0.50 |
2.6 |
38.7 |
1 X 400.0 |
2013/0.50 |
2.8 |
43.5 |
1 X 500.0 |
1769/0.60 |
3.0 |
46.5 |
1 X 630.0 |
2257/0.60 |
3.0 |
51.5 |
6382TQ 2 Core Type 450/750V EPR/HOFR Trailing Rubber Cable
Core and Size
Mm sq |
Stranding (Number of Strand/Strand Diameter |
Nominal Thickness of Insulation mm |
Nominal Overall Diameter mm |
2 X 1.0 |
32 / 0.2 |
0.8 |
7.3 |
2 X 1.5 |
30 / 0.25 |
0.8 |
8.1 |
2 X 2.5 |
50 / 0.25 |
0.9 |
9.5 |
2 X 4.0 |
56/0.30 |
1.0 |
11.4 |
2 X 6.0 |
84/0.30 |
1.0 |
13.6 |
2 X 10.0 |
80/0.40 |
1.2 |
17.5 |
2 X 16.0 |
126/0.40 |
1.2 |
19.8 |
2 X 25.0 |
196/0.40 |
1.4 |
27.5 |
6383TQ 3 Core Type 450/750V EPR/HOFR Trailing Rubber Cable
Core and Size
Mm sq |
Stranding (Number of Strand/Strand Diameter |
Nominal Thickness of Insulation mm |
Nominal Overall Diameter mm |
3 X 1.0 |
32 / 0.2 |
0.8 |
7.8 |
3 X 1.5 |
30 / 0.25 |
0.8 |
8.6 |
3 X 2.5 |
50 / 0.25 |
0.9 |
10.1 |
3 X 4.0 |
56/0.30 |
1.0 |
15.5 |
3 X 6.0 |
84/0.30 |
1.0 |
17.5 |
3 X 10.0 |
80/0.40 |
1.2 |
22.5 |
3 X 16.0 |
126/0.40 |
1.2 |
26 |
3 X 25.0 |
196/0.40 |
1.4 |
29.5 |
3 X 35.0 |
276/0.4 |
1.4 |
34 |
3 X 50.0 |
396/0.40 |
1.6 |
38.5 |
3 X 70.0 |
360/0.50 |
1.6 |
43.6 |
3 X 95.0 |
475/0.50 |
1.8 |
50 |
3 X 120.0 |
608/0.50 |
1.8 |
53.9 |
3 X 150.0 |
756/0.50 |
2.0 |
59.9 |
3 X 185.0 |
925/0.50 |
2.2 |
65.9 |
3 X 240.0 |
1221/0.50 |
2.4 |
73.5 |
3 X 300.0 |
1525/0.50 |
. |
81 |
6384TQ 4 Core Type 450/750V EPR/HOFR Trailing Rubber Cable
Core and Size
Mm sq |
Stranding (Number of Strand/Strand Diameter |
Nominal Thickness of Insulation mm |
Nominal Overall Diameter mm |
4 X 1.0 |
32 / 0.2 |
0.8 |
8.8 |
4 X 1.5 |
30 / 0.25 |
0.8 |
9.6 |
4 X 2.5 |
50 / 0.25 |
0.9 |
11.3 |
4 X 4.0 |
56/0.30 |
1.0 |
15.5 |
4 X 6.0 |
84/0.30 |
1.0 |
17.5 |
4 X 10.0 |
80/0.40 |
1.2 |
23.1 |
4 X 16.0 |
126/0.40 |
1.2 |
28.1 |
4 X 25.0 |
196/0.40 |
1.4 |
32.5 |
4 X 35.0 |
276/0.4 |
1.4 |
37 |
4 X 50.0 |
396/0.40 |
1.6 |
43 |
4 X 70.0 |
360/0.50 |
1.6 |
48 |
4 X 95.0 |
475/0.50 |
1.8 |
55 |
4 X 120.0 |
608/0.50 |
1.8 |
61.2 |
4 X 150.0 |
756/0.50 |
2.0 |
73 |
4 X 185.0 |
925/0.50 |
2.2 |
80 |
4 X 240.0 |
1221/0.50 |
2.4 |
81.5 |
4 X 300.0 |
1221/0.50 |
2.6 |
84.5 |
6385TQ 5 Core Type 450/750V EPR/HOFR Trailing Rubber Cable
Core and Size
Mm sq |
Stranding (Number of Strand/Strand Diameter |
Nominal Thickness of Insulation mm |
Nominal Overall Diameter mm |
5 X 1.5 |
30 / 0.25 |
0.8 |
10.7 |
5 X 2.5 |
50 / 0.25 |
0.9 |
12.5 |
5 X 4.0 |
56/0.30 |
1.0 |
17.2 |
5 X 6.0 |
84/0.30 |
1.0 |
19.5 |
5 X 10.0 |
80/0.40 |
1.2 |
26 |
5 X 16.0 |
126/0.40 |
1.2 |
30.5 |
5 X 25.0 |
196/0.40 |
1.4 |
36 |
5 X 35.0 |
276/0.40 |
1.4 |
43 |
5 X 50.0 |
396/0.40 |
1.6 |
45.5 |
638XTQ Multicore Type 450/750V EPR/HOFR Trailing Rubber Cable
Core and Size
Mm sq |
Stranding (Number of Strand/Strand Diameter |
Nominal Thickness of Insulation mm |
Nominal Overall Diameter mm |
7 X 1.5 |
30 / 0.25 |
0.8 |
13.7 |
7 X 2.5 |
50 / 0.25 |
0.9 |
15.7 |
7 X 4.0 |
56/0.30 |
1.0 |
18.7 |
7 X 6.0 |
84/0.30 |
1.0 |
22.4 |
7 X 10.0 |
80/0.40 |
1.2 |
27.7 |
7 X 16.0 |
126/0.40 |
1.2 |
31.6 |
7X 25.0 |
196/0.40 |
1.4 |
38.4 |
8 X 1.5 |
30 / 0.25 |
0.8 |
14.8 |
8 X 2.5 |
50 / 0.25 |
0.9 |
17.2 |
8 X 4.0 |
56/0.30 |
1.0 |
20.4 |
12 X 1.5 |
30 / 0.25 |
0.8 |
16.5 |
12 X 2.5 |
50 / 0.25 |
0.9 |
19.3 |
12 X 4.0 |
56/0.30 |
1.0 |
22.9 |
18 X 1.5 |
30 / 0.25 |
0.8 |
19.7 |
18 X 2.5 |
50 / 0.25 |
0.9 |
22.9 |
18 X 4.0 |
56/0.30 |
1.0 |
27.3 |
21 X 1.5 |
30 / 0.25 |
0.8 |
21.9 |
21 X 2.5 |
50 / 0.25 |
0.9 |
25.8 |
27 X 1.5 |
30 / 0.25 |
0.8 |
23.8 |
27 X 2.5 |
50 / 0.25 |
0.9 |
27.9 |
37 X 1.5 |
30 / 0.25 |
0.8 |
26.9 |
37 X 2.5 |
50 / 0.25 |
0.9 |
32.9 |
42 X 1.5 |
30 / 0.25 |
0.8 |
30.4 |
42 X 2.5 |
50 / 0.25 |
0.9 |
35.7 |
|